How to reset the Accumulated Power Consumption (APH) parameter in Altivar 71 Drive.

You can reset the APH parameter with below procedure. It can only be possible with the Graphic display terminal.

·         Enter in the menu Identification 1.11.
·         Select and hold ENTER for 2s on the software version of Graphic S (For example 1.2IE06 - line below "GRAPHIS S" text).
·         Enter the menu Diagnostic 1.10.
·         Go to "Test procedure" sub menu.
·         Go to "Run Elapsed Time Reset" (ETR) submenu.
·         Select "Operating t.reset", then press ENTER.
·         Select "rest kWh" by pressing the ENTER.
·         Recycle the Drive power.