Why for the same apparent power, the nominal current of the transformer and the generators are different in My Ecodial L.

This difference is due to the fact that the nominal current of the transformer is calculated by using the voltage at no-load
and the nominal current of the generator is calculated by using the rated voltage. The use of the voltage at no-load is provided by
the IEC 60076-1 standard.