What is the principle of operation for Magnetic Latching Contactor CR1F.

The latching function is due to the magnetic circuitry used in CR1F** contactors.
 
There are two inputs on the coil
  1. Input to latch the contactor (A1) and
  2. Input to release the contactor (E1).
 
On sending a pulse on A1 (1 to 2 seconds) the contactor closes and stays closed until a second pulse is sent on E1 (1 to 2 seconds) to release the contactor.
 
The wiring diagram below provides more details.